User manual - ATR144- 55
47
P. b . M .1
Proportional Band Multiplier 1
Proportional band multiplier for heating/cooling P.I.D.
for process 1. Proportional band for cooling action is
given by parameter P.B. 1 multiplied for this value
1.00...5.00. Default: 1.00
48
o.d.b.1
Overlap / Dead Band 1
Dead band combination for heating / cooling P.I.D.
(double action) for process 1.
-20.0%...50.0%
Negative: Dead band.
Positive: overlap. Default: 0.0%
49
c. c. t.1
Cooling Cycle Time 1
Cycle time for cooling output in heating/cooling P.I.D.
mode for process.
1-300 seconds (Default: 10 sec.)
50
L.L. P.1
Lower Limit Output Percentage 1
Selects min. value for command output percentage.
0%...100%, Default: 0%.
51
U . L . p .1
Upper Limit Output Percentage 1
Selects max. value for command output percentage.
0%...100%, Default: 100%.
52
m . G . t .1
Max Gap Tune 1
Sets the max. process-setpoint allowed gap before
the automatic tune recalculates PID parameters of the
process.
0-10000 [digit
1 p. 86
] (degrees.tenths for temp. sensors).
Default: 2.0