14  Table of anomaly signals
If installation malfunctions, the controller switches off 
the regulation output and reports the anomaly noticed. 
For example, controller will report failure of a connected 
thermocouple visualizing e -05 (flashing) flashing on display.
For other signals see table below.
Cause What to do
E-02
SYSTEM Erro r
Cold junction 
temperature sensor 
failure or environment 
temperature out of 
range
Call assistance
E-04
eeprom 
Erro r
Incorrect configuration 
data. Possible loss of 
instrument calibration
Verify that 
configuration 
parameters are 
correct.
E-05
PRob e 1 
Erro r
Sensor connected 
to AI1 broken or 
temperature out of 
range
Control connection 
with probes and 
their integrity.
E-0 7
seri aL erro r
Communication error 
in modbus master
Check the 
configuration 
parameters and 
the RS485 serial 
connection
E-0 8
SYSTEM Erro r
Missing calibration Call assistance
E-8 0
rfi d Erro r
RFID tag malfunction Call assistance