14 Table of anomaly signals
If installation malfunctions, the controller switches off
the regulation output and reports the anomaly noticed.
For example, controller will report failure of a connected
thermocouple visualizing e -05 (flashing) flashing on display.
For other signals see table below.
Cause What to do
E-02
SYSTEM Erro r
Cold junction
temperature sensor
failure or environment
temperature out of
range
Call assistance
E-04
eeprom
Erro r
Incorrect configuration
data. Possible loss of
instrument calibration
Verify that
configuration
parameters are
correct.
E-05
PRob e 1
Erro r
Sensor connected
to AI1 broken or
temperature out of
range
Control connection
with probes and
their integrity.
E-0 7
seri aL erro r
Communication error
in modbus master
Check the
configuration
parameters and
the RS485 serial
connection
E-0 8
SYSTEM Erro r
Missing calibration Call assistance
E-8 0
rfi d Erro r
RFID tag malfunction Call assistance