User manual - DRR244 - 47
diS A b.
Special functions disabled
SWAP
Shows the setpoint on display 1 and the process on display 2 (only if Par. 278 vi . d . 2 set
on
c .1 . S P v )
285
n Fc.L.
NFC Lock
diS A b.
NFC lock disabled: NFC accessible.
En A b.
NFC lock enabled: NFC not accessible.
286
s.k.s.f.
Set Key Special Functions
Assign special functions to the SET button. To execute the function the button must be pressed
for 1 second.
diS A b.
No special function linked to the SET key. (Default)
st./s t.
Start/Stop. Pressing SET key the controller switches from Start to Stop and viceversa.
Status of the controller, upon power-up, depends on parameter ini.s.
2 t.s wi.
2 Threshold Command Setpoint Switch. The controller changes the regulation setpoint
alternating between Set1 and Set2
3 t.s wi.
3 Threshold Command Setpoint Switch. The controller changes the regulation setpoint
alternating between Set1, Set2 and Set3
4 t.s w i.
4 Threshold Command Setpoint Switch. The controller changes the regulation setpoint
alternating between Set1, Set2, Set3 and Set4
A.i. 0
Analogue Input 0. Set analogue input to zero (zero tare)
GROUP S -
ct
- Current Transformer
287
ct F.
Current Transformer Function
Enables the C.T. input and selects the net frequency
DiS a b.
Disabilitato (Default)
50 Hz
50 Hz
60 Hz
60 Hz
288
ct v.
Current Transformer Value
Selects the amperometric transformer full-scale
1.. 2 0 0
Ampere (Default: 50)
289
rEs .
Reserved
Reserved parameter
290
H.b.a.t.
Heater Break Alarm Threshold
Heater Break Alarm activation threshold
0
Alarm disabled. (Default:)
0.1-200.0
Ampere.
291
ocu. t.
Overcurrent Alarm Threshold
Overcurrent alarm threshold.
0
Alarm disabled. (Default)
0.1-200.0
Ampere
292
H.b.a.d.
Heater Break Alarm Delay
Heater Break Alarm and overcurrent alarm activation delay.
00:00-60:00
mm:ss (Default: 01:00)
293÷297 Reserved Parameters - Group S
Reserved parameters - Group S