48 - DRR244 - User manual
GROUP T -
a. o . 1
- Retransmission 1
298
r t M .1
Retransmission 1
Retransmission for AO1 output. Parameters 300 and 301 define lower and upper limit of the
operating scale.
diS a b.
Disabled (Default)
c.1.S P v
Command 1 setpoint
A L. 1
Alarm 1 setpoint
A L. 2
Alarm 2 setpoint
Md.b us
Retransmits the value written on word 1241
A.iN.1
Value read on input AI1
AMPer.
Ampere from current transformer
299
r.1 . t y .
Retransmission 1 Type
Selects the retransmission type for AO1
0.1 0 v
Output 0...10 V.
4.20ma
Output 4...20 mA. Default
300
r.1. L.L.
Retransmission 1 Lower Limit
Retransmission 1 lower limit range (value related to 10 V or 0/4 mA).
-9999..+30000 [digit
1 p. 54
] (degrees if temperature), Default: 0.
301
r.1. u.L.
Retransmission 1 Upper Limit
Retransmission 1 upper limit range 2 (value related to 10 V or 20 mA).
-9999..+30000 [digit
1 p. 54
] (degrees if temperature), Default: 1000.
302
r .1 . s . e .
Retransmission 1 State Error
Determines retransmission 1 value in case of error or anomaly
If the retransmission output is 0-10V:
0 V
0 V. Default
10 v
10 V.
If the retransmission output is 0-20 mA or 4-20 mA:
0 ma
0 mA. Default
4 ma
4 mA.
20 ma
20 mA.
21.5 m a
21.5 mA.
303÷307 Reserved Parameters - Group T
Reserved parameters - Group T
GROUP U -
res.
- Reserved
308÷317 Reserved Parameters - Group U
Reserved parameters - Group U