10 - TCT101-1ABC - User manual
Potentiometer:
To modify Set1 or Set2 by external potentiometer follow the 
steps below:
1  use potentiometers 5kOhm to 10kohm 
2  connect cursor to pin I3; a wrong connection may damage 
the potentiometer and lead to lock of the device.
3  accuracy on input is max 1000 points, therefore set the 
parameters “Upper limit” and “Lower limit” with a max 
difference of 1000 units. (Ex.: LoS1 to 50,0 and u PS1 to 
150,0 to modify time value related to Set1 between 50 and 
150 seconds with steps of one tenth). Greater differences 
would make unstable the less significant digit.
4 To calibrate the scale of potentiometer enter the 
configuration mode and select:
 Hi n . 3 as Pot
 Fi n . 3  as Set1 or Set2
 P. tA r as Enable
  Exit configuration mode and place potentiometer at 
minimum level and press ¶ key, then place potentiometer 
at max level and press premere § key: the device 
automatically exit the calibration procedure.
N.B.: a switch-off of the device would interrupt the calibration.