EasyManua.ls Logo

Polyaire Zonemaster Variable Air Volume - Commissioning; Initiating and Exit Setting Process

Default Icon
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 8
2) Take off the small cover on the top of the
damper controller and set a special address
forthebypassdampercontroller.
3)
Use a pre-tested control cable to
connectthebypassdamper
controllertothe‘point’socketonthe
main controller board. Make sure
theredlightonthedampercontroller
ison.Otherwise,checkthecableand
the connection.
COMMISSIONING
TheZonemasterVAVsystemhasseveralparametersthatmustbesetin
thecommissioningstage.
Zonetouchpad(3button)canonlysetthreezoneparameters:
1)
Touchpad Address
2)
Temperature Sensor
3)
Minimum Ventilation
Mastertouchpad(6button)cansettheaboveparametersandthree
systemparameterslistedbelow:
1) SupplyAirSafetyHigh&LowLimits
2) SpillBypass/AirSetpoint
3) NamingZones
1.InitiatingandExitSettingProcess
1) Holddownbothandbuttonsforabout
5secondsuntiltheLCDdisplays‘Setting’onthe
top line of the LCD screen.

Related product manuals