FEATURES
• Manualandtimeprogrammablezonetemperaturecontrol.
• Supportsupto16zones.
• Addressofeachzoneissetdirectlyfromthetouchpad.
• Maintainsroomtemperaturewithin±1°Cusinganonboardsensor.
• LCDindicatorforzonestatusandparameterdisplay.
• User-friendlytemperatureandprogramsetting.
• Realtimeclockwithbatterybackup.
• 5-1-1programmabletemperaturesettingpointandstarttime.
• Personalisedzonelabelling.
• Autospill/bypass---thedesignatedzones/bypassareforced
open when all zones are turned off.
• Safetysystem---Opensalldampersifthesupplyair
temperatureislessthanlowlimitormorethanhighlimit.
• Allzonesautomaticallyreturntotheiroriginalon/offstateonce
power up.
APPLICATION
TheZonemasterVAV(VariableAirVolume)isafullyfeaturedsystem
designedtoaccuratelymanageairowbyzoneinDuctedreversecycle,
heatingandevaporativeairconditioningsystems.
ItmanagesairowfromtheA/Cunitbyassessingtemperaturesineach
zoneandopeningandclosingdamperstoincreaseordecreaseairowto
achieve and maintain a preset temperature in that zone.
The temperature difference that the Zonemaster can achieve will not be
lower(cooling)orhigher(heating)thanthetemperaturesetbytheACunit.
Page 1