110-392 29
Technical Information
Controller Specifications
Temperature Set Point Resolution ±0.1°C
Temperature Stability ±0.5°C (±0.9°F)
Temperature Units °C or °F
Pressure Units PSI or kPa
Pressure Display Resolution 1 PSI / 0.1 kPa
Flow Rate Units GPM or LPM
Flow Rate Display Resolution 0.1 GPM / 1 LPM
Performance Specifications
Model Air-Cooled
58XX & 68SS Series
Water-Cooled
59XX & 69XX Series
Compressor Nominal HP 1.5
Temperature Range
(without heater option)
°F
°C
41° to 95°F
5° to 35°C
Temperature Range
(with heater option)
°F
°C
41° to 194°F
5° to 90°C
Temperature Stability °F
°C
±0.9°F
±0.5°C
Cooling Capacity
1
Tons
Watts
BTU/hour
1.48
5200
17,732
1.8
6328
21,600
Nominal Evaporator Flow
2
US GPM 3.72 4.3
Refrigerant R134A
Pressure
3
PSIG 60
Pump
3
HP 1/3
Fan(s) HP 1/6 N/A
Condenser Discharge Air Flow CFM 1070 N/A
Water Condenser Flow – Tower Water US GPM N/A 5.4
Water Condenser Connections Inches N/A 0.75
Process Connections (inlet / outlet) Inches 0.5
Reservoir Tank Capacity US Gallons (liters) 3.5 (13.25)
Dimensions (L x W x H) Inches
cm
30.5 x 19 x 26”
78 x 48 x 66 cm
Shipping Weight Pounds
kg
340
154
1. Capacity of air-cooled units based on 68°C (20°C) entering air and 68°F (20°C) leaving water; capacity of water-cooled units based on
85°F (29°C entering water.
2. Chiller flow rate based on 2.4 US GPM ton (0.54m
3
/hr/ton).
Environmental Conditions Indoor use only
Maximum Altitude: 2000 meters
Operating Ambient: 5° to 35°C
Relative Humidity: 80% for temperatures to 30°C
Installation Category: II
Pollution Degree: 2