5. MAINTENANCE
Code Descripon Soluon
E12 High exhaust temp. protecon
1. Replace the compressor exhaust temperature sensor.
2. Reconnect or clean compressor exhaust temperature
sensor and wrap it with insulaon tape.
3. Replace the controller or PC Board.
E15 Water inlet temperature fault Check the connecon, change the sensor if necessary.
E16 External coil temperature fault Check the connecon, change the sensor if necessary.
E18 Exhaust temperature fault Check the connecon, change the sensor if necessary.
E19 DC fan motor fault
Check DC fan motor. Change it if damaged. Check output
port of DC fan motor on PCB. Change the PCB if there is
no output.
E20
Abnormal protecon of frequency
conversion module
Solve it according to the subsidiary error codes in the
following table.
E21 Ambient temperature fault Check the connecon, change the sensor if necessary.
E23
Low outlet water temp protecon
when cooling
Check the water ow and water system, mend it if
necessary.
E27 Water outlet temperature fault Check the connecon, change the sensor if necessary.
E28 CT over current protecon
E29 Sucon temperature fault Check the connecon, change the sensor if necessary.
E32
High outlet water temperature
protecon when heang
Check the water ow and water system,mend it if
necessary
E33
Outdoor coil high temperature
protecon
Wait for the ambient temperature drops and restart the
unit.
E42 Internal coil temperature fault
The E20 fault displays specic error codes, detailed in the following table.
Error codes 1 to 128 are displayed in priority. Error codes 257 to 384 are only displayed if the
previous ones do not appear.
If two or more error codes appear at the same me, then the error codes accumulate.
For example, if codes 8 and 16 occur at the same me, the display shows 24.