MC shifting, PC absolute: Pumped heating circuits are blocked until the
DHW has been heated up. Should the boiler capacity not be sufficient,
the mixer circuit will also be restricted.
For more information, see
Delay heat request (746, 1046, 1346), page 90
Legionella function (1640)
Function to kill legionella germs by heating up to the set legionella function
setpoint (see programme number 1645).
Off: Legionella function is switched off.
Periodically: Legionella function is repeated periodically, depending on
the set value (prog. no. 1641).
Fixed weekday: Legionella function will be activated on a certain
weekday (prog. no. 1642).
Legionella funct periodically (1641)
Setting the interval for the legionella function periodically (recommended
setting in case of additional drinking water heating by solar plant in
connection with a storage tank mixing pump).
Legionella funct weekday (1642)
Selection of the weekday for the legionella function.
Legionella funct time (1644)
Setting the start time for the legionella function. With setting --- the
legionella function will be carried out the first time DHW heating is
enabled.
Legionella funct setpoint (1645)
Selecting the set temperature required for killing the bacteria.
Legionella funct duration (1646)
With this function, the time is set during which the legionella function
setpoint is activated to kill germs.
Important
If the colder storage tank temperature rises to above the legionella
function setpoint -1 K, the legionella function setpoint is
considered as met and the timer starts running. If the storage tank
temperature drops by more than the switching difference +2K
below the required legionella function setpoint, the duration has to
be met again. If no duration has been set, the legionella function is
met immediately when the legionella function setpoint is reached.
Legionella funct circ pump (1647)
On: The circulation pump will be switched on in case of active legionella
function.
Warning
When legionella function is active, there is a risk of scalding at the
draw-off points.
Circulating pump release (1660)
Time program 3/HC3: The circulating pump is released subject to time
program 3 (see prog. no. 540 to 556).
DHW release: The circulating pump is released when DHW heating is
released.
Time program 4/DHW: The circulating pump is released subject to time
program 4.
Time program 5: The circulating pump is released subject to time
program 5.