EasyManua.ls Logo

PowerShield Commander 1100 - UPS Setting

PowerShield Commander 1100
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 OPERATIONS continued
3-5. UPS Setting
There are three parameters to set up the UPS.
Parameter 1: For program alternatives. Refer to below table.
Parameter 2 & 3: The setting options or values for program.
01 Output voltage setting
Interface Setting
For 208/220/230/240 VAC models, you may choose the following
output voltage:
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac (Default setting)
02 Programmable outlets enable/disable
Interface Setting
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default setting)
03 Programmable outlets setting
Interface Setting
Set up the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode. (Default setting: 999)
14
Parameter 2 Parameter 1
Parameter 3