This parameter is valid only for asynchronous motors.
V/F slip compensation can compensate for the speed deviation of asynchronous motor
when the increases, so as to keep stable speed when the load changes.
If V/F slip compensation gain is set to 100.0%, it means that the compensated
deviation is equal to the rated motor slip under the rated motor load, while the rated
motor slip can be calculated through b0 group of motor rated frequency and rated speed.
When adjust V/F slip compensation gain, generally it is based on the principle that the
motor speed is same as the target speed. When the motor speed is different from target
value, it is necessary to appropriately fine-tune the gain.
If the above parameters need to be displayed in operation, firstly set its position to 1, and
then set at F6.01 after converting the binary number to the hexadecimal number.