6 Control of the backwashing valves
NOTICE!
The default state of the backwashing valves is deener‐
gised (voltage free)
Fault: No backwashing is possible if the backwashing
valves cannot be controlled.
Consequence: The hygiene parameters worsen and
the hydraulic resistance of the filter increases.
Measure: Regularly check (dependent on the applica‐
tion) the operation of filter backwash.
An automatic 6-way valve cannot be used.
For backwashing there is, for example, the option of controlling a
Besgo
®
rod valve.
To do this, the rod valve must be connected to terminal P3 in the P
module. If two circuits are in operation, the second rod valve must
be connected to terminal P2.
To activate this function, the function
[Backwash 1]
or
[Backwash 2]
must be activated in the P module.
Setting of the backwashing times is described under Timer set‐
ting
Ä Chapter 4 ‘Timer settings’ on page 12
.
n Which day or which sequence
n Which backwashing, 1 or 2
n Start time
n Reduction time
n Duration of the backwashing backwash time
Control of the backwashing valves
15