M714_User_Master.doc
Updated Aug. 25, 2015 44
3.10 Modifying Variable Cycles 1 of 2
Variable Cycles may be used where varying
make-up conductivity cause water treatment fault.
Requires a make-up conductivity sensor
.
Key ENTER
.
.
.
.
Key DOWN to Variable Cycles and key ENTER
.
.
.
.
.
.
Key ENTER to modify Low Range
.
.
When the Make-up Conductivity is
less than Low Range
Bleed is controlled at Low Cycles
.
Key ENTER to modify the Low Cycles
.
.
.
.
.
.
Key ENTER to modify Medium Range
.
.
When the Make-up Conductivity is
less than Medium Range & greater than Low Range
Bleed is controlled at Medium Cycles
.
.
Key ENTER to modify the Medium Cycles
.
.
Conductivity E
1384 uS
Tower Bleed 2
ON: 8.6 min
Tower Bleed 2
Timed Events
Setup
Variable Cycles
Tower Bleed 2
Variable Cycles.....
Low Range
350 uS
Tower Bleed 2
Variable Cycles.....
Low Cycles
6.100 cycles
Tower Bleed 2
Variable Cycles.....
Med. Range
650 uS
Tower Bleed 2
Variable Cycles.....
Med. Cycles
4.250 cycles
then
or
or
or
or
Continued on Page 2