EasyManua.ls Logo

ProSoft Technology MVI56E-MCM - Page 64

ProSoft Technology MVI56E-MCM
209 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration as a Modbus Slave MVI56E-MCM ControlLogix Platform
User Manual Modbus Communication Module
Page 64 of 209 ProSoft Technology, Inc.
MVI Address
0xxx
1xxxx
3xxxx
4xxxx
Tag Address
1200
3201 to 3216
40191
ReadData[200]
1500
8001 to 8016
40491
ReadData[500]
1598
9569 to 9584
40589
ReadData[598]
1599
9585 to 9600
40590
ReadData[599]
With the offset parameters listed above, the Modbus Master could read from coils
10001 to 10176 using the tags MCM.DATA.WRITEDATA[0] TO [9]. The Master
could also read from address 30001 to 30490, and the data contained in those
Modbus addresses would come from the tags MCM.DATA.WRITEDATA[10] TO
[499] within the ControlLogix program.
The Master could then write to coils addressing 0001 to 0160 and this data would
reside within the ControlLogix program in tags MCM.DATA.READDATA[0] TO [9].
The Master could then write to registers using Modbus addresses 40001 to
40590, and this information would reside in addresses
MCM.DATA.READDATA[10] TO [599].
Note: The offset parameter only sets the starting location for the data. As shown above, if the
Master issues a Write command to address 40001, the data will go into the ControlLogix processor
at address MCM.DATA.READDATA[10].
Likewise, a Write To bit address 0161 will also change to address
MCM.DATA.READDATA[10].0 within the program. Be careful not to overlap your
data. You may want leave additional registers/bits unused to allow for future
expansion in the program.

Table of Contents

Other manuals for ProSoft Technology MVI56E-MCM

Related product manuals