27
4.7.3 Battery number setting (PCS)
Interface
Setting
When EP is ON, turn to battery number setting page[PCS], it’s
required password to enter page(default password: 135).
1KVA/1KW 3PCS(default) >> 1KVA/1KW 2PCS
2KVA/2KW 6PCS(default) >> 2KVA/2KW 4PCS
3KVA/3KW 8PCS(default) >> 3KVA/3KW 6PCS
6KVA/6KW 16PCS(default) >> 6KVA/6KW 20PCS
10KVA/10KW 16PCS(default) >> 10KVA/10KW 20PCS
NOTE:
1. Battery number setting is only for long-run UPS model.
2.
When sending UM0 command to set as long-run model, the default
battery number is
1KVA(3PCS)/2KVA(6PCS)/3KVA(8PCS)/6KVA(16PCS)/10KVA(16PCS),
and cannot be modified.
Set UPS 3KVA battery number to 6 PCS.
4.7.4 Emergency power off setting (EPO)
Interface
Setting
When EP is ON, turn to emergency power off setting page[EPO].
By default, the EPO is valid(OFF) by pulling out the EPO terminal,
and it can be changed to be valid(ON) by inserting the EPO terminal.
Set EPO to ON.