28
4.7.5 Battery end of discharge voltage setting (EOd)
Interface
Setting
When EP is ON, turn to battery end of discharge voltage setting
page[EOd]. You can set EOd as below value: dEF(default), 9.8V,
9.9V,10V,10.2V,10.5V.
Battery end of discharge voltage varies with load:
10.5V: @load<25%,
10.2V: 25%<@load<50%,
10V: @load > 50%.
Set EOd to 10.5V.
4.7.6 ECO setting (ECO)
Interface
Setting
When EP is ON, turn to ECO setting page[ECO].
You may choose the following two options:
OFF: ECO mode disable (Default)
ON: ECO mode enable