ECTIFICATION OF FAULTS
There are basically two kinds of system fault:
•
Faults that are recognised by the control unit and which it can therefore indicate
•
Faults that cannot be indicated by the control unit
10.1 Faults with error message
Error display Possible causes Action
Flashing
•
Sensor cable
interrupted
•
Sensor defective
Check cables
Check sensor resistance value,
replace sensor if necessary
Flashing
•
Short circuit in sensor
wiring
•
Sensor defective
Check cables
Check sensor resistance value,
replace if necessary
Circulation error:
no flow rate
Flashing
Additionally in the case of
energy yield estimation:
•
Error in pump
connection
•
Pump defective
•
Air in the system
•
Flow rate counter
defective
•
Connection to flow rate
meter defective
•
Sensor cable
interrupted
•
Sensor defective
Check cabling
Replace pump
Bleed system
Check whether, when the system is
running, the impeller wheel of the
meter moves (if visible)
Check cables
Check cables
Check sensor resistance value,
replace sensor if necessary