Factory Defaults 
When first installing the IMP+ i.s., or subsequently moving or using the unit 
on a new application, before proceeding to program the unit for its intended 
application it is recommended that you ensure that all parameters are at their 
default values by completing a Factory Defaults P930, as described in 
Chapter 5 Parameter Guide. 
 
 
When you first switch the IMP+ i.s. on, it will be reading the distance from 
the face  of  the  transducer  to  the material  surface.  It  will  be  indicating in 
metres, as shown on the display.  
 TIP 
In some applications, it is simplest to empty the 
vessel, take a reading from the Imp for distance 
and then setup the empty level to this figure. 
 
Once you are satisfied with the installation, and the IMP+ i.s. is reading what 
you would expect in terms of distance from the face of the transducer to the 
material  level,  then  you  can  proceed  with programming,  for  the intended 
application. It is sensible to program all the required parameters at the same 
time. The system will be then set-up.  
Note that the span is automatically calculated from the empty level, so the 
empty level should be entered first.