Chapter 5 Parameter Guide
This chapter describes all the parameters in your IMP+ i.s..
Parameter Listing
This section describes all the parameters contained within the IMP+ i.s..
Application (APP) Menu
P100 Mode of Operation
This parameter sets the mode of operation, when in run mode, and can be set
to one of the following:
Display shows the distance from the
transducer face to the surface.
Display shows how full the vessel is.
Display shows how empty a vessel is.
Display shows volume of material in the
vessel
P104 Measurement Units
This parameter sets the units you want to use for programming and display
All units of measure are METRES
All units of measure are CENTIMETRES
All units of measure are MILLIMETRES
All units of measure are FEET
All units of measure are INCHES
P105 Empty Level
This parameter is to be set to the maximum distance from the face of the
transducer to the empty point, in P104 Measurement Units. Note this value
affects span as well, so should be set before span. Default: IMP 3 = 3.00m
(9.94 feet), IMP 6 = 6.000m (19.69 feet) and IMP 10 = 10.00m (32.81
feet).