Page 35 
Chapter 6   Troubleshooting 
This  section  describes  many  common  symptoms,  with  suggestions  as  to 
what to do. 
Display  blank,  transducer  not 
firing. 
No valid echo being received and unit 
has  gone  into  fault  condition.  Check 
material  level  is  not  out  of  range, 
sensor  is  perpendicular  to  material 
surface. 
Incorrect  reading  being 
displayed for current level. 
Measure actual distance from 
transducer face to surface of material. 
Enter Program Mode and access SyS1 
menu, go to P21 and press ENTER 
type in the measured distance, press 
ENTER, wait until “Stor” is 
displayed and return to Run Mode, 
display should now update to correct 
reading.  
Material  level  is  consistently 
incorrect by the same amount. 
Check  empty  level  (P105)  correctly 
entered.