EasyManua.ls Logo

Pulsar Imp+i.s. - Test (tESt) Menu; P991 Hard Test; P992 mA Out Test

Pulsar Imp+i.s.
43 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 28
P605 Volume Units
This parameter determines the units that will be used in calculating volume
conversion. It is used in conjunction with P607 (maximum volume), please
note that there is no provision for the volume unit’s descriptor to be shown
on the display.
The choices are:
Option
Description
0 = No Units
Volume will be totalised with no units
1 = Tons
Volume will be totalised in Tons
2 = Tonnes
Volume will be totalised in Tonnes
3 = Cubic metres
Volume will be totalised in cubic metres
4 = Litres
Volume will be totalised in litres
5 = UK Gallons
Volume will be totalised in UK Gallons
6 = US Gallons
Volume will be totalised in US Gallons
7 = Cubic feet
Volume will be totalised in cubic feet
8 = Barrels
Volume will be totalised in barrels
P606 Correction Factor
This parameter is used to enter a correction factor, when required, such as
the specific gravity of the material so that the volume calculated is relative
to the actual amount of material that can be contained between empty level
(P105) and 100% of span (P106). Default = 1
P607 Max Volume
This parameter displays the actual maximum volume that has been
calculated by the IMP+ i.s., i.e. P604 Calculated Volume x P606 Correction
Factor, and is a Read Only parameter. The volume displayed will be shown
in P605 Volume Units and is the total volume available between empty
level (P105) and 100% of span (P106).

Table of Contents

Related product manuals