To  program  the  Level  Star  3  for  Example  3  Volume  Application  with 
Control by using the Quick Setup menu proceed as follows. 
If required access the Program Mode  
Key in the passcode 1997 and press ENTER 
Using the ‘right’ arrow key go to the Quick Setup menu press ENTER and 
as prompted, by the questions, select the relevant option and ENTER. 
The  unit  knows  that  only  Relay  3  is 
available  and  so  will  automatically  set 
Alarm 2 to Relay 3. 
0 = Cylindrical Flat Base 
Enter  Vessel  Dimensions  as  requested 
(depends on vessel shape chosen) 
Displays the Max Volume as calculated 
by the Level Star 
 
This  example  is  for  a  cylindrical  flat-bottomed  vessel.  See  P600  Vessel 
Shape in the following Parameter Guide, for a description of all the other 
vessel  shapes  you  could  select.  Some  vessel  shapes  require  additional 
dimensions to be entered, and you will be asked for these during quick set-
up. 
Programming is now complete and the unit can be returned to the run mode, 
press CANCEL until Run Mode? Is displayed on the LCD press ENTER, 
and the Level Star will return to the Run Mode.