INSTALLER/DEALER SETTINGS
Setting
Default
Description
Loss of Supervisory Signals for Z-
Wave
4
Select the length in hours (4, 24) before reporting a loss of supervision on Z-Wave Sirens.
Loss of Supervisory Signals for Non
Emergency Sensors
24
Select the length in hours (4, 12, 24) before reporting a loss of supervision on security
devices.
NOTE: For UL/cUL Resi Fire and UL Commercial Burg (UL2610) the wireless supervision window for Non-Emergency
sensors (all intrusion sensors) shall be set to 4h. These devices shall not be used for EN Grade 2 compliant installations
Loss of Supervisory Signals for
PowerG Non Emergency Sensors
24
Select the length of time (20, 30 min, 1, 2, 4, 12, 24 hours) before reporting a loss of
supervision on PowerG security devices.
NOTE: For UL/cUL Resi Fire and UL Commercial Burg (UL2610) the wireless supervision window for Non-Emergency
sensors (all intrusion sensors) shall be set to 4h. For EN Grade 2, the supervision window shall be set for 20 minutes.
Loss of Cell Signal Timeout
30
Select the length in minutes (10-120) before reporting a loss in cellular signal.
NOTE: For UL Commercial Burg (UL2610) the cell supervision is hardcoded to 200s
Communication Test
Monthly
Choose Never, Daily, Weekly or Monthly when enabling the communication test.
NOTE: For UL Resi Fire (UL985) the test frequency shall be set to Weekly. By default the system will be set to Weekly if
UL985 is selected on Alarm.com
Communication Test Start Time
Randomized
Select the time of day that the panel will send its Communication Test. If no time is
selected the time will automatically be randomized.
QOLSYS CONFIDENTIAL AND PROPRIETARY
PAGE OF 29 197
PROGRAMMING

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the QOLSYS IQ4 Hub and is the answer not in the manual?

QOLSYS IQ4 Hub Specifications

General IconGeneral
BrandQOLSYS
ModelIQ4 Hub
CategoryControl Panel
LanguageEnglish

Related product manuals