EasyManua.ls Logo

Quadra-Fire EXCURSION-I - 4 Installation Preparation; Cleaning; Flue Damper; Gas Line

Quadra-Fire EXCURSION-I
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
Quadra-Fire • EXCURSION-I, EXCURSION-II, EXCURSION-III Installation Manual • 2538-980 Rev. E • 5/19
4
Installation Preparation
Prepare the existing solid fuel masonry or factory built
non-combustible rebox for installation.
A. Cleaning
Prior to installing the gas insert:
• Ensure that the woodburning replace cavity is clean
and free of ash, soot, and other debris.
B. Flue Damper
Fully lock the solid fuel replace’s ue damper in the open
position, OR completely remove it.
C. Gas Line
Note: If the factory built replace has no gas access hole
provided, an access hole of 1 inch (25 mm) diameter or
less may be drilled through the lower sides or bottom of the
rebox in a proper workmanship - like manner. This access
hole must be plugged with non-combustible insulation after
the gas supply line has been installed.
• Install gas line to the factory provided ex line. See
Figure 4.1.
• Check local codes and gas line sizing requirements
following NFPA54. See Section 7.
• It is recommended that extra length of gas line be
installed within the existing wood burner or masonry
replace to allow removal of the insert for future servicing
needs.
D. Fireplace Conversion Notice
The replace conversion notice is included in the appliance
manual bag. Permanently attach the label with the follow-
ing warning to the inside lower back of the replace rebox
into which the insert is being installed. Silicone or mechani-
cal fasteners may be required to properly secure the label.
WARNING! Risk of Fire! This replace has been con-
verted for use with a gas replace insert only and cannot
be used for burning wood or solid fuels unless all original
parts have been replaced, and the replace re-approved
by the authority having jurisdiction.
E. Electrical Outlet Box
An outlet box may be installed in a bottom back corner of
the existing solid fuel masonry or factory built replace
to power the appliance. Each unit ships standard with a
cord assembly to permit blowers or other optional acces-
sories to be used. The accessories plug into the new out-
let box or may be routed out onto the hearth to a nearby
outlet.
ELECTRICAL OUTLET LOCATIONS
MASONRY
MASONRY
APPLIANCE
RECOMMENDED
NOTICE: DO NOT wire 110-120 VAC to wall switch.
Figure 4.2 Electrical Outlet Detail
Figure 4.1
Appliance Size Left Side Right Side
25 in. 10 ft. 6 in. 8 ft.
30 in. 10 ft. 3 in. 7 ft. 6 in.
35 in. 10 ft. 7 ft.
Appliance Cord Length (approximate)

Table of Contents