CT100 Thermostat
Z Wave
®
Anti-theft
The Anti-Theft Command Class disables a subset of supported/
controlled command classes in the thermostat if the thermostat is
being disconnected from and reconnected to a Z-Wave network.
(This thermostat supports version 2 of the Anti-Theft Command
Class.) This command class is typically used when installing a
thermostat in a public location, such as a hotel room or conference
center. The command class allows the user to lock the thermostat to
the actual Z-Wave network and to render it useless if it is removed
from the local network without being unlocked. Another application
would be to protect service-provider-owned products from leaving
the service providers network before they are paid for.
Disabled Commands With Engaged Anti-Theft protection
Basic Command Clock Command
Indicator Command Manufacturer Specifi c Command
Multilevel Sensor Command Thermostat Mode Command
Thermostat Operating State
Command Thermostat Fan Mode Command
Thermostat Fan State Command Thermostat Setpoint Command
Version Command Confi guration Command
Battery Command Association Command
Anti-theft Command
Multi Channel Command
(Only supported if a humidity sensor is
present.)
CT100 Thermostat
Z Wave
®
Confi guration Parameters
This device supports the following Confi guration Parameters:
Name Set/Get Default Values
1 Temp Reporting Threshold Set/Get 2 0 to 4
2 HVAC Settings Get Only N/A see below
3 Utility Lock Enable/Disable Set Only 0 0 to 127
4 C- Wire/Battery Status Get Only N/A 0 or 1
5 Humidity Reporting Threshold Set/Get 2 0 to 3
6 Auxiliary/Emergency Set/Get 0 0 or 1
7 Thermostat Swing Temp Set/Get 2 1 to 8
8 Thermostat Diff Temp Set/Get 4 4 to 12
9 Thermostat Recovery Mode Set/Get 2 1 or 2
10 Temp Reporting Filter Set/Get see below
11 Simple UI Mode Enable/Disable Set/Get 1 0 or 1
12 Multicast Enable/Disable Set/Get 0 0 or 1
1. Temperature Reporting Threshold (8-bit)
This value determines the reporting threshold when association
reporting is enabled. Unsupported values are ignored.
Value
0 1 2 3 4
Treshhold
Disabled Disabled 0.5°F 1.0°F 1.5°F
2. HVAC Settings (32-bit)
Byte 1 = HVAC Setup: Normal (0x01) or Heat Pump (0x02)
Byte 2 = Aux Setup (Gas (0x01) or Electric (0x02)) & Number of
Auxiliary Stages (Heat Pump)/Number of Heat Stages
(Normal)
Byte 3 = Number of Heat Pump Stages
Byte 4 = Number of Cool Stages
3. Utility Lock (8-bit)
If set to 0, the utility lock is disabled. All other values (1-255) enable
the utility lock.