FX1- 4N1 Control Settings
RANDELL CONTROL SETTINGS FX1-4N1
DIXELL PART NUMBER XB570L-4R0F1
RANDELL PART NUMBER RF CNT0703
CODE LOCKED NO CODE
Prb READ PROBE - Prb
rPr ROOM TEMPERATURE PROBE READING
READ
ONLY
rPr
Epr EVAPORATOR PROBE TEMPERATURE READING
READ
ONLY
Epr
iPr INSERT TEMPERATURE PROBE READING
READ
ONLY
iPr
Pr1 USER VARIABLE PARAMETERS - Pr1
HY HYINTERVENTION DIFFERENTIAL FOR SET POINT 4 HY
AC ANTI-SHORT CYCLE DELAY 1 AC
tCY DURATION OF LAST CYCLE
READ
ONLY
tCY
tP1 DURATION OF FIRST PHASE OF THE LAST CYCLE
READ
ONLY
tP1
tP2 DURATION OF SECOND PHASE OF THE LAST CYCLE
READ
ONLY
tP2
tP3 DURATION OF THIRD PHASE OF THE LAST CYCLE
READ
ONLY
tP3
PR2 INSTALLER PARAMETERS - PR2
PAS PASS CODE 321 PAS
HY HYINTERVENTION DIFFERENTIAL FOR SET POINT 4 HY
AC ANTI-SHORT CYCLE DELAY 1 AC
PAU TIME OF STANDBY 0 PAU
PFt MAXIMUM ACCEPTANCE DURATION OF POWER FAILURE 15 PFt
Con COMPRESSOR ON TIME WITH FAULTY PROBE 15 Con
COF COMPRESSOR OFF TIME WITH FAULTY PROBE 15 COF
rPO THERMOSTAT PROBE CALIBRATION 0 rPO
EPP EVAPORATOR PROBE PRESENCE YES EPP
EPO EVAPORATOR PROBE CALIBRATION 0 EPO
i1P INSERT PROBE 1 PRESENCE NO i1P
i1o INSERT PROBE 1 CALIBRATION 0 i1o
i2P INSERT PROBE 2 PRESENCE NO i2P
i2o INSERT PROBE 2 CALIBRATION 0 i2o
i3P INSERT PROBE 3 PRESENCE NO i3P
i3o INSERT PROBE 3 CALIBRATION 0 i3o
rEM END CYCLE PROBE SELECTION RPT rEM
CF TEMPERATURE MEASUREMENT UNITS F CF
rES RESOLUTION (%%DC ONLY) IN rES
Lod UPPER DISPLAY VISUALIZATION RP Lod
rEd REMOTE DISPLAY, X-REP, VISUALIZATION RP rEd
d1P DOOR SWITCH INPUT POLARITY OP d1P
odc COMPRESSOR AND FAN STATUS WHEN OPEN DOOR F-C odc
doA OPEN DOOR ALARM DELAY 5 doA
dLc STOP COUNTDOWN OF THE RUNNING CYCLE WITH DOOR OPEN YES dLc