9.5.3 HLT HV
Connect the high voltage from the CAPO to the shorten high voltage terminals of the transformer.
Connect the measurement Input A to the shorten low voltage terminals of the transformer.
Connect the measurement Input B to the shorten tertiary voltage terminals of the transformer.
If you start the measurement, it will do the following 3 measurements:
GSTg B
C
H
+ C
HL
GSTg A+B
C
H
UST A
C
HL
9.5.4 HLT LV
Connect the high voltage from the CAPO to the shorten low voltage terminals of the transformer.
Connect the measurement Input A to the shorten high voltage terminals of the transformer.
Connect the measurement Input B to the shorten tertiary voltage terminals of the transformer.
If you start the measurement, it will do the following 3 measurements:
GSTg A
C
L
+ C
LT
GSTg A+B
C
L
UST B
C
LT