27
Stage Settings Submenu
H1 Stage Up Range: 0 – 30 minutes Default: 0 (0=disabled)
If setpoint is not met by the stage up time, a forced stage up to stage 2 heating occurs.
H2 Stage Up Range: 0 – 30 minutes Default: 0 (0=disabled)
If setpoint is not met by the stage up time, a forced stage up to stage 3 heating occurs
C1 Stage Up Range: 0 – 30 minutes Default: 0 (0=disabled)
If setpoint is not met by the stage up time, a forced stage up to stage 2 cooling occurs
Number of Heat Stages: Range: 1-3 Default: 2
Number of Cool Stages: Range 1-2 Default: 2
Max Heat SP Range: 40F to 109F (5C-33C) Default: 85F (29C)
Sets the maximum heating setpoint value. Will not ramp or accept setpoints higher that this maximum.
Min Cool SP Range: 44F to 113F (9C-37C) Default: 50F (10C)
Sets the minimum cooling setpoint value. Will not ramp or accept setpoints lower than this minimum.
Minimum Run Time Range: 1- 9 Minutes Default: 3
Sets the minimum run time before a heating/cooling cycle can turn off.
Sets heating/cooling cycle time. Prevents rapid cycling.
Minimum Off Time Range: 5-9 Minutes Default: 5
Sets the minimum off time before another heating/cooling cycle can begin. Provides compressor short
cycle protection.
SmartVent Submenu
Vent Enable Range: Y or N Default: N
Enables the SmartVent feature. SmartVent control screen will show up in the Main Menu.
Inside Temp Zone Range: 1-6 Default: 2 (defaults to 1 with the ZCV1)
Vent Time Range: 1- 99 seconds Default: 30
Vent Delta Range: 4-9 Default: 5
Vent MRT Range: 1-120 Default: 4
Vent MOT Range: 1-30 Default: 10
EQ Settings Submenu Not Applicable to the ZCV1 control Unit
Security System Submenu
Security Enable Range: Y or N Default: N
Setback Enable Range: On or OFF Default: ON
Zone Fan Purge Range: 0-120 seconds Default: 30
Delta T Settings
Note on Delta Settings : The Delta T setting is the delta, or difference, between the setpoint and
current temp for determining when a heat or cool call comes on. The “delta” is the number of
degrees away from the current setpoint.