H/C Delta Range: 0 - 15 degrees. Default: 4
Sets the minimum separation between heating and cooling setpoints. Attempts to lower the
cooling below the heating setpoint by this amount will PUSH the heating setpoint down to maintain
this separation. Same for setting the heating setpoint above the cooling setpoint, it will PUSH the
cooling setpoint up to maintain this separation.
Heating Delta Stage 1 ON Range: 1 to 8 degrees Default: 1
Sets the delta below setpoint that stage 1 heating starts.
Heating Delta Stage 2 ON Range: 1 to 8 degrees Default: 3
Sets the delta below setpoint that stage 2 heating starts.
Heating Delta Stage 3 ON Range: 1 to 8 degrees Default: 5
Sets the delta below setpoint that stage 3 heating starts.
Cooling Delta Stage 1 ON Range: 1 to 8 degrees Default: 1
Sets the delta above setpoint that stage 1 cooling starts.
Cooling stage 1 turns on at: Setpoint + Delta Stage 1 On
Cooling Delta Stage 2 ON Range: 1 to 8 degrees Default: 3
Sets the delta above setpoint that stage 2 cooling starts.
Cooling stage 2 turns on at: Setpoint + Delta Stage 2 On
Fan Cycler Submenu
The fan cycler function cycles the HVAC system fan for an ON period followed by an Off period
continuously. Used to provide minimum air ventilation requirements. When the Fan ON time is
set to a value greater than 0, an additional “Cycler” FAN mode is present in the FAN Mode
screen.
Fan ON Time Range: 0-120 minutes Default: 0 (=OFF)
Fan OFF Time Range: 0-120 minutes Default: 20
Remote Sensors Submenu
RS1 Type Range: A, Type 2, Type 3 Default: Type 2
RS2 Type Range: A, Type 2, Type 3 Default: Type 2
RS2 Location Range: IN only Default: IN
Splash Timer Range: 0-120 seconds Default: 0 (0=Off)
Turns on the logo splash screen for 3 seconds every set interval.
WDU Settings Submenu
Messaging Enable Range: Y or N Default: N
Enables messaging feature. Message screen shows up in the Main Menu when enabled.
Restore Defaults Submenu
Restore defaults? Range Y or N Default: N