PROGRAM VALUE FOR ALARM #2
The range of the alarm value is -99,999 to 999,999.
“AL-2” < > “-99999” to “999999”
PROGRAM HYSTERESIS VALUE FOR ALARM #2 (Cannot be
programmed if alarm latch is programmed)
The hysteresis (deadband) value for alarm #2 may be programmed from 1 to
999,999. The value is either added to or subtracted from the alarm value depending
on whether the alarm is high or low acting. (See “alarms” section for operation.)
“HyS-2” < > “1” to “999999”
ALARM #2 HIGH OR LOW ACTING
The action of alarm #2 may be programmed to activate either when the signal
goes above the alarm value (high acting) or goes below it (low acting).
“Act-2” < > “HI” or “LO”
Note: Depending on options selected under Pro 3 and Pro 6, alarms, hysteresis,
peak, and valley values can be monitored and/or changed when PGM. DIS.
is tied to COMM. This provides a “QUICK PROGRAMMING” method for
“day to day” process changes. (See QUICK PROGRAMMING SECTION
for more details.)
-16-