PROGRAMMING EXAMPLE
As an example of a programming sequence, the following values, gained from a
flow application, are programmed into the indicator.
DISPLAY: 100.0 gallons/minute at 4.000 mA
3000.0 gallons/minute at 20.000 mA Resolution of 0.1 gallons. Minimal
filtering. Activate alarm #1 output when flow falls below 100 Gallons/min,
activate display alarm. Peak and valley (max/min) readings for each day to be
recorded.
TOTALIZER: When total exceeds 8000.0 then latch alarm #2 which stops flow.
Alarm must be manually reset. Reset alarm #2 by remote input. Disable
totalization when flow falls below 100.0
SERIAL: Provide hardcopy print-out of total, input and peak/valley when operator
actuates print request. Baud rate 300.
ANALOG RE-TRANSMISSION: Reverse acting output for control value 4mA
at 2000.0 g/min and 20 mA at 0.0 g/min.
“Pro 1”.....“dECPNt” - Enter 0.0
“round” - Enter 0.1
“SCALE” - Enter yes
“dSP 1” - Enter 100.0
“INP 1” - Apply 4.000 mA
“dSP 2” - Enter 3000.0
“INP 2” - Apply 20.000 mA
“SEGt” - Enter 1
“Pro 2”.....Not required since scaling
done in “Pro 1”.
“Pro 3”.....“dECPNt” - Enter yes
“ENt AL” - Enter yes
“dSPHYS” - Enter no
“rSt AL” - Enter no
“dSPbUF” - Enter yes
“rStbUF” - Enter yes
“SELdSP” - Enter yes
“rSttOt” Enter yes
“tArE” - Enter no
“Pro 4”..... “dECPNt” - Enter 0
“E1-CON” - Enter 8 (reset alarm #2)
“E2-CON” - Enter 14 (print request)
“Pro 5”.....“dECPNt” - Enter 0.0
“tbASE” - Enter 1
“SCLFAC” - Enter 1.000
“Lo-cut” - Enter 100.0
“Pro 6”.....“trAc” - Enter no
“dISP” - Enter yes
“LAtC-1” - Enter no
“ASN-1” - Enter input
“AL-1” - Enter 100.0
“HYS-1” - Enter 1.0
“Act-1” - Enter LO
“LAtC-2” - Enter yes
“ASN -2” - Enter total
“AL-2” - Enter 8000.0
“HYS-2” - N/A
“Act-2” - Enter HI
“Pro 7”.....“bAud” - Enter 300
“AddrES” - Enter 0
“Print” - Enter 6
“FULL” - Enter yes
“Pro 8”.....“ASIN” - Enter input
“AN-Lo” - Enter 2000.0
“AN-HI” - Enter 0.0