ELECTROMAGNETIC COMPATIBILITY
Immunity to EN 50082-2
Electrostatic discharge EN 61000-4-2 Level 2; 4 Kv contact
1
Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m
2
80 Mhz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms
150 Khz - 80 MHz
Power frequency magnetic fields EN 61000-4-8 Level 4; 30 A/m
Simulation of cordless telephones ENV 50204 Level 3; 10 V/m
900 Mhz, ±5 MHz
200 Hz, 50% duty cycle
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A
Notes:
1. Metal bezel of unit connected with ground lead from rear bezel screw to metal
mounting panel.
2. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
Process and analog output signals may vary during EMI disturbance.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
Refer to the EMC Installation Guidelines section of the manual for additional
information.
21. CONSTRUCTION: Die-cast metal front bezel that meets NEMA 4/IP65
requirements for indoor use when properly installed. Case body is black, high
impact plastic (panel gasket and mounting clips included). Pollution Degree 2.
22. CONNECTION: Removable terminal blocks
23. WEIGHT: 1.2 lbs (0.5 kg)