RCF manual Chapter 19 BACnet signals 53
Object name Object ID Description Unit Writeable
RC_Setp_R.RegioRoomTempRemote Analog value, 15 Remote control of room
°C Yes
RC_Setp_R.RegioStandbySetPDeadBan
Analog value, 16 Deadband for Standby mode °C Yes
Not used in this model Analog value, 17-26
RC_Setp_R.RegioMinECFanSpeed Analog value, 27 Lowest possible speed for the
% Yes
RC_Setp_R.RegioMaxFanSpeed Analog value, 28
Highest possible speed for the
EC fan
% Yes
RC_Setp_R.RegioAIChangeOverLimitL
ow
Analog value, 29 Cooling if lower change-over
temperature
°C Yes
RC_Setp_R.RegioAIChangeOverLimitH
igh
Analog value, 30 Heating if higher change-over
temperature
°C Yes
RC_Setp_R.RegioThermostatHyst Analog value, 31 Room temperature hysteresis °C Yes
RC_Setp_R.RegioComfortSetPDeadban
d
Analog value, 32 Deadband for comfort mode. °C Yes
RC_SetpExt_R.RegioRCFSetPoint Analog Value, 33 Basic setpoint for the
controller
°C Yes
RC_Actual_R.RegioPID2Setp Analog Value, 34 Calculated supply air setpoint °C No
Binary inputs
Object name Object ID Description Values Writeable
RC_Actual_L.RegioDIOpenWindow Binary input, 0 Indicates open window ACTIVE/
INACTIVE
No
Not used in this model Binary input, 1
No
RC_Actual_L.RegioDIPresences Binary input, 2 Indicates presence from
digital input
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioDIChangeOver Binary input, 3 Indicates change-over
from digital input
ACTIVE/
INACTIVE
No
Not used in this model Binary input, 4-6 No
All binary inputs have normal polarity