54 Chapter 19 BACnet signals RCF manual
Binary values
Object name Object ID Description Values Writeable
Not used in this model Binary value, 0 No
RC_Actual_L.RegioCVHeatPulsProp Binary value, 1 Indicates pulse prop. heating ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVCoolPulsProp Binary value, 2 Indicates pulse prop. cooling ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVHeatInc Binary value, 3 Indicates heating increase ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVHeatDec Binary value, 4 Indicates heating decrease ACTIVE/
INACTIVE
No
Not used in this model Binary value, 5-6 No
RC_Actual_L.RegioChangeOverState Binary value, 7 Indicates change-over status
from both digital and
analogue input
ACTIVE/
INACTIVE
No
Not used in this model Binary value, 8 No
RC_Actual_L.RegioFireAlarmStop Binary value, 9 Places the unit in Shutdown
mode and prevents it from
being activated again, unless
this value is first set to “0”.
ACTIVE/
INACTIVE
Yes
RC_Setp _L.RegioShutDown Binary value, 10 Places the unit in Shutdown
mode
ACTIVE/
INACTIVE
Yes
RC_Setp_L.RegioBlockConfig Binary value, 12 Prevents parameter menu
access via display
ACTIVE/
INACTIVE
Yes
All binary values have normal polarity
Loop
Object name Object ID Description
Controller Loop, 0 The Regio controller