EasyManuals Logo

Regin RCF Series User Manual

Regin RCF Series
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
54 Chapter 19 BACnet signals RCF manual
Binary values
Object name Object ID Description Values Writeable
Not used in this model Binary value, 0 No
RC_Actual_L.RegioCVHeatPulsProp Binary value, 1 Indicates pulse prop. heating ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVCoolPulsProp Binary value, 2 Indicates pulse prop. cooling ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVHeatInc Binary value, 3 Indicates heating increase ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVHeatDec Binary value, 4 Indicates heating decrease ACTIVE/
INACTIVE
No
Not used in this model Binary value, 5-6 No
RC_Actual_L.RegioChangeOverState Binary value, 7 Indicates change-over status
from both digital and
analogue input
ACTIVE/
INACTIVE
No
Not used in this model Binary value, 8 No
RC_Actual_L.RegioFireAlarmStop Binary value, 9 Places the unit in Shutdown
mode and prevents it from
being activated again, unless
this value is first set to “0”.
ACTIVE/
INACTIVE
Yes
RC_Setp _L.RegioShutDown Binary value, 10 Places the unit in Shutdown
mode
ACTIVE/
INACTIVE
Yes
RC_Setp_L.RegioBlockConfig Binary value, 12 Prevents parameter menu
access via display
ACTIVE/
INACTIVE
Yes
All binary values have normal polarity
Loop
Object name Object ID Description
Controller Loop, 0 The Regio controller

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Regin RCF Series and is the answer not in the manual?

Regin RCF Series Specifications

General IconGeneral
BrandRegin
ModelRCF Series
CategoryController
LanguageEnglish

Related product manuals