B 7 - Solar system with 2 collector fields (East/West) and zone valve
Sensor connection - max. 12V Mains voltage - 230V 50Hz
Low voltage - sensor connection
Terminal: connection for:
S1 (2×) sensor 1 collector 1
S2 (2×) sensor 2 storage tank
S3 (2×) sensor 3 collector 2
The polarity of the sensors is freely selectable.
Mains voltage - 230V 50Hz
Terminal: connection for:
L mains phase conductor L
N mains neutral conductor N
R1 pump L (speed)
N pump N
R2 zone valve L
N zone valve N
PE protective conductor (green-yellow)
Note: Actuating direction of zone valve:
R2 off = valve closed = flow direction AB-B = flow from collector field 1 (sensor S1)
R2 on = valve open = flow direction AB-A = flow from collector field 2 (sensor S3)
R1 output: for speed control of standard pumps, minimum load 20VA.
B 8 - Solar system with 2 collector fields and 2 pumps
Sensor connection - max. 12V Mains voltage - 230V 50Hz
Low voltage - sensor connection
Terminal: connection for:
S1 (2×) sensor 1 collector 1
S2 (2×) sensor 2 storage tank
S3 (2×) sensor 3 collector 2
The polarity of the sensors is freely selectable.
Mains voltage - 230V 50Hz
Terminal: connection for:
L mains phase conductor L
N mains neutral conductor N
R1 pump (coll. 1) L
N pump (coll. 1) N
R2 pump (coll. 2) L
N pump (coll. 2) N
PE protective conductor (green-yellow)
R1 output: for speed control of standard pumps, minimum load 20VA.
max. 12V 230VAC
Sensor side
Danger
Danger
Mains side
Mains
230VAC
Optional
Caution
Caution
max. 12V 230VAC
Sensor side
Danger
Danger
Mains side
Mains
230VAC
Optional
B
AB
A