34
R
EGULUS - SRS 3 Controller - www.re
g
ulus
.
eu
Special functions menu 7
D 7 - Special functions
Menu „7. Special functions” is used to set basic
items and expanded functions.
Menu „7. Special functions” is used to
set basic items and expanded functions.
The menu is closed by pressing „esc” or selecting
„Exit special functions”.
D 7. 1 - Program selection menu 7.1
The suitable hydraulic variant for the specic application is selected and set here (see Chapter A2 Hydraulic
variants). The associated diagram can be displayed by pressing „info”.
Setting range: Program selection 1-20 / default setting: 1
Normally the program selection is made only once during initial commissioning by the specialist.
Incorrect program selection can lead to wrong operation and unpredictable errors.
D 7. 2 - Time & date menu 7.2
This menu is used to set the current time and date.
For analysis of the system data it is essential for the time to be set accurately on the controller.
Please note that the clock does not continue to run if the mains voltage is interrupted, and must
therefore be reset.
D 7. 3 - Sensor calibration menu 7.3 / 7.3.1 - 7.3.3
Deviations in the temperature values displayed, for example due to cables which are too long or sensors
which are not positioned optimally, can be compensated for manually here. The settings can be made for each
individual sensor in steps of 0.5 °C.
Setting range: Offset S1...S3 -100 °C to +100 °C / default setting: 0 °C
Settings are only necessary in special cases at the time of initial commissioning by the specialist.
Incorrect measurement values can lead to wrong operation and unpredictable errors.
D 7. 4 - Commissioning help menu 7.4
Starting the commissioning help guides you in the correct order through the basic settings necessary for
commissioning, and provides brief descriptions of each parameter in the display.
Pressing the „esc” key takes you back to the previous value so you can look at the selected setting again or
adjust it if desired. Pressing the „esc” more than once takes you back to the selection mode, thus cancelling
the commissioning help. (see also C3 Commissioning help).
May only be started by a specialist during commissioning! Observe the explanations for the
individual parameters in these instructions, and if further settings are necessary for your
application, set them after the help is nished.
D 7. 5 - Reset to factory settings menu 7.5
All of the settings that have been made can be reset, thus returning the controller to its delivery state.
The entire parameterization, analyses, etc. of the controller will be lost irrevocably. The controller
must then be commissioned and set once again.
Danger
Caution
Caution
Caution
Caution
Caution