23
Implementing pipe cleaning openings
Install a branch instead of a 45° bend at
redirection points.
Provide additional outlet with a dummy
plug (see Fig. 5-18).
Remove dummy plug for cleaning.
Fig. 5-18: Cleaning opening
Connecting central vacuum unit to
vacuum pipes
Connect vacuum pipes to the central
vacuum unit with RAUPIANO Plus double
sleeve.
Securing vacuum pipes
Recommended spacing of pipe brackets:
for horizontal pipes: up to 0.5 m
for vertical pipes: up to 1.0 m
Secure vacuum pipes with fixed brackets
or guide brackets mounted to the wall with
hanger bolts and plastic plugs.
Attach fixed brackets directly after the
sleeve.
For lengths of 1 m or longer, use guide
brackets as well.
5.6
Central vacuum unit
The central vacuum unit may be installed in a
basement, storage room, utility room or
garage. The site selected should ensure that
vacuum and exhaust air pipes can be kept as
short as possible.
Demands on the site of installation:
Lowest room in the entire system
Room temperature between 5 °C and
25 °C all year round
Ventilate room well, ventilation aperture to
the outside at least 150 cm
2
Mains power connection
Sufficient space for emptying collected dirt
and servicing work
Observe the following when installing the
radio receiver unit:
Allow a distance of at least 2 m between
central vacuum unit and radio receiver unit.
Do not install central vacuum unit and
radio receiver unit behind steel doors.
If this cannot be avoided, the radio receiver
unit must be installed at a site with
favourable reception outside the room with
the steel door.
Do not install radio receiver unit in the fuse
box or in the vicinity of other wireless
control units.
Mounting central vacuum unit
Fig. 5-19: Mounting wall mount
Fit vibration dampers (2) in the wall mount
(1).
Fix wall mount (1) to the wall at a height of
approx. 1.6 m using screws (3), washers
(4) and wall plugs (5) (see also mounting
instructions (Brochure No. 00F2064).
Using screw and wall plug, fix spacer (6) at
a distance of x below the centre of the wall
mount (1).
Suspend central vacuum unit on wall
mount so that it hangs straight.
Checking the cartridge filter
The central vacuum unit comes pre-fitted
with the cartridge filter.
Check that the cartridge filter is firmly in
place before starting the system.
Warning!
Risk of death!
Ignitable/explosive gasses and mixtures
can cause death, severe burns and
damage to property.
Ensure that no ignitable/explosive
gasses or liquids are found in the room.
Do not install central vacuum unit in
explosion-hazardous areas.
Warning!
Risk of death!
Short circuits at the central vacuum unit
resulting from high humidity can cause
death, severe burns and damage to
property.
Do not install central vacuum unit in
rooms exposed to moisture.
Central vacuum unit
Model
Distance x
2000 and 3000 17 cm
4000 33 cm
Caution!
Damage to property!
Defective cartridge filters can cause
damage to property.
Only operate the system with
undamaged cartridge filter.
Check cartridge filter regularly.
x
1
3
4
2
5
6