20
REMKO GPS series
Type B23 vertical
L1 maximum duct length without end pieces
Pipe ø 80
Model Metres
GPS 15 30
GPS 25 30
GPS 35 30
GPS 55 25
GPS 75 10
L1
Mounting height
2.5 - 3.5 m
S
K
Type B23 vertical through the ceiling.
NOTE
Condensate drainage connection [K] = M 20 external thread
Type C13 horizontal / coaxial
L1 + L2 maximum duct length without end pieces
Pipe ø 80 Pipe ø 100
Model Metres
GPS 15 30 + 30 -
GPS 25 30 + 30 -
GPS 35 20 + 20 -
GPS 55 8 + 8 20 + 20
GPS 75 2 + 2 10 + 10
Gas fireplace type C
Room-air-independent combustion system.
The combustion cycle is sealed compared
to the environment in which it is installed.
The combustion air is fed from outside.
The ductwork runs horizontally through the outside
wall or vertically through the roof.
Flue gas and fresh air adapter piece Ø80 to Ø100
GPS 55-75; EDP no.: 228916
Type C13
Room-air-independent combustion system.
Exhaust/ and combustion air are led through an LAS
end piece through the outside wall.
NOTE
According to Section 4-1-2 of the FeuVO (German
Fire Ordinance), only fireplaces that are self-con-
tained from indoor air may be operated in garages.
L1
L2
2,5 - 3,5 m
750 mm
Installation height