REOVIB MFS 368
Operating instructions
23
10.0 Troubleshooting
Error messages
If there is an error, a message flashes in the first line of the display.
Error_2401/2402 Acc sensor fault: Acc. sensor not connected, or defective.
Error_0005 Overvoltage: Mains input voltage too high.
Error_0002 Overload: Output power exceeded e.g. wrong frequency set, magnetic air gap too large.
Error_0088 Overcurrent: Defective coil, earth fault, defective cable.
Error_0001 Track Timeout: If sensor timeout function is exceeded.
Error_0112 Control overheated
Error_0113 Feeder coil overheated: (signal from external temperature switch)
Error_0087 Peak current: Set frequency too low for coil used, or frequency changes too fast with this
setting.
Acknowledgement with the menu item Service -> Execute error. For most (but not all) errors,
pressing the green "I" key will suffice.
Display shows the symbol
Check the connection and the
Enable parameters.
Display shows the symbol
pressed.
Press the green button
"Start / Reset".
Check if the feeder is properly
connected.
2401/2402
properly connected.
does not start
Display shows a static frequency
Switch "Auto. freq." On.
does not start
Feeder vibration amplitude is
small
Increase the setpoint.
does not start
Feeder vibration amplitude is
large
Check the sensor's mounting
location.
Check the V/g ratio of the sensor.
stops at the limit value "Min.
freq."
the limit value "Min. freq."
Check the setting.
stops at the limit value "Max.
freq."
the limit value "Max. freq."
Check the setting.
deviates from the resonant
frequency
commissioning, it is possible that
the frequency converter initially
shifts away from the resonant
frequency. In this case, the search
will reverse at the frequency
limits and move back towards the
resonant frequency.