The relay allocated to the function block is switched on,
when the adjusted switch-on temperature (Th(x)on) is
reached. It is switched off when the adjusted switch-off
temperature (Th(x)off) is reached. The switching condi-
tions of all other activated functions of the function block
have to be fullled as well.
Allocate the reference sensor in the expert menu.
Adjust the maximum temperature limitation with Th(x)off
> Th(x)on and the minimum temperature limitation with
Th(x)on > Th(x)off. The temperatures cannot be set to an
identical value.
Thermostat function
(Function block 1 … 5):
Arrangement/Options/Thermo1 (...10)
selection: „Yes“, „No“
factory setting: „No“
Arrangement/adj. values/Th1(...10)on
adjustment range: - 40,0 … 250,0 °C
factory setting: 40,0 °C
Arrangement/adj. values/Th1(...10)off
adjustment range: - 40,0 … 250,0 °C
factory setting: 45,0 °C
Arrangement/Expert/Sen-Th1 (...10)
adjustment range: 1 … 10
factory setting: 3 (...10)
The relay allocated to the function block is switched on as
soon as the adjusted switch-on temperature (DTh(x)on) is
reached. It is switched off as soon as the adjusted switch-off
temperature (DTh(x)off) is reached. The switching condi-
tions of all other activated functions of the function block
have to be fullled as well.
DT-function (function block 1 5):
Arrangement/Options/DT-func 5 (...9)
selection: „Yes“, „No“
factory setting: „No“
Arrangement/adj. values/DT5(...9)on
adjustment range: 1,0 50,0 K
factory setting: 5,0 K
Arrangement/adj. values/DT5(...9)off
adjustment range: 0,5 50,0 K
factory setting: 3,0 K
Arrangement/Expert/Sen 1-DT5(...9)
adjustment range: 1 … 10
factory setting: 3 (...10)
Arrangement/Expert/Sen 2-DT5(...9)
adjustment range: 1 … 10
factory setting: 4 (...10)
Each timer function provides up to 21 time frames (3 for
each day). The relay allocated to the function block is acti-
vated as long as the time frame (t(x)on t(x)off) is open.
The switching conditions of all other activated functions of
the function block have to be fullled as well.
Timer function (function block 1 5):
Arrangement/Options/timer 1 (...5)
selection: „Yes“, „No“
factory setting: „No“
Arrangement/adj. values/timer 1 (...5)/t1(...21)-on
adjustment range: 00:00 … 00:00
factory setting: 22:00
Arrangement/adj. values/timer 1 (...5)/t1(...21)-off
adjustment range: 00:00 … 00:00
factory setting: 05:00
Adjust the reference sensor in the expert menu.

Other manuals for Resol DeltaSol E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resol DeltaSol E and is the answer not in the manual?

Resol DeltaSol E Specifications

General IconGeneral
BrandResol
ModelDeltaSol E
CategoryController
LanguageEnglish

Related product manuals