DeltaSol
®
E
© RESOL 20160310 DeltaSol_E_V2.monen.indd
| 34
Internal heating circuit control:
Arrangement/heat. circuit/Options/hc
selection: „Yes“, „No“
factory setting: „No“
4.2.1 Heating circuits:
The controller can control up to 4 independent weather-
compensated heating circuits. One heating circuit can be
controlled via the internal control functions and the oth-
ers via an additional external module RESOL HKM3 each.
The TFlow-value indicates the measured actual ow tem-
perature of the heating circuit.
The Temperature-outdoor-value indicates the measured
outdoor temperature depending on wheather conditions.
The ow set temperature is calculated from the measured
outdoor temperature and the heating curve. Onto this,
the dial setting of the remote control (RTA11-M) and the
controller day correction or night correction are added.
Flow set temperature = heating curve temperature + re-
mote control + (day correction or night correction). If the
calculated ow set temperature is higher than the adjust-
ed maximum ow temperature, the ow set temperature
will be equated with the maximum ow temperature.
The internal heating circuit is activated in this menu.
Arrangement/heat. circuit/HC/Tflow
Flow temperature
Arrangement/heat. circuit/HC/Toutd
Outdoor temperature
Arrangement/heat. circuit/hc/flow set
Set ow temperature
Display of heating circuit status (summer, day, night, defect).
Arrangement/heat. circuit/hc/Hc Stat.
Status heating circuit
Display of afterheating status (on, off).
Arrangement/Heat. circuit/hc/afterh.
Status afterheating
Display of store temperature(s) of the heating circuit af-
terheating.
Arrangement/Heat. circuit/hc/T(2)st
Store temperature 1 (2)
Adjustment channel for night correction (night set back)
of the heating circuit. For the night correction function,
time frames (see below) can be adjusted. Within these
timeframes, the set ow temperature of the curve will be
decreased (set back) by the adjusted temperature value.
Adjustment channel for the day correction function of the
heating circuit. The day correction function is always ac-
tive outside the 3 time frames of the night correction
function. The ow set temperature of the curve will be
decreased or increased by the adjusted temperature value.
Night correction:
Arrangement/Heat. circuit/hc/night corr.
adjustment range: -20 … +30 K
factory setting: -5 K
Day correction:
Arrangement/Heat. circuit/hc/day corr.
adjustment range: -5 … +45 K
factory setting: 5 K
Adjustment channel for the admissible maximum ow
temperature of the heating circuit. If the maximum ow
temperature is exceeded, the heating circuit will be
switched off (the mixer will close).
Maximum ow temperature:
Arrangement/Heat. circuit/hc/Tflowmax
adjustment range: 10 … +100 °C
factory setting: 50 °C

Other manuals for Resol DeltaSol E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resol DeltaSol E and is the answer not in the manual?

Resol DeltaSol E Specifications

General IconGeneral
BrandResol
ModelDeltaSol E
CategoryController
LanguageEnglish

Related product manuals