Translation of the Original ENGLISH PERIODICAL INSPECTIONS AND TESTS
454522.68.07-01-E
39
27.06.2012
The visual inspection comprises the following:
− Inspection of the air filter elements on the condenser for cleanliness
− Inspection of the seal of the expansion valve
− Visual inspection of the refrigeration circuit for oil leaks in the area of the compressor and
condenser connecting lines (suction line, pressure line)
− Inspection of the condenser heat exchanger surface and the refrigerant piping for corrosion
damage
− Inspection of the mounting and attachment of all piping and components for security
− Visual inspection of the water circuits under operating conditions for leaks
− Check that the operating manual is available at the P030 Chiller
Notice!
• All periodical inspections and tests must be documented in the system logbook.