1.5 Safety Requirements
Operation of P030 Chillers within the European Union:
The following information applies to P030 Chillers with closed refrigeration cycles that are used
within the European Union. In some member states additional requirements may apply, e.g. due to
environmental considerations.
The P030 Chillers contain components whose working pressures are subject to the regulations laid
down in the Pressure Equipment Directive 97/23/EC and European standard EN 378 (Parts 1 − 4,
most recent version).
Apart from the requirements relating to the design, equipment and testing of the P030 Chiller prior
to delivery to the customer, also the operator of such systems has to comply with requirements in
accordance with European standard EN 378 and possibly additional national regulations. These
concern the installation, the operation and periodical inspections/tests of P030 Chillers.
1.5.1 Installation
The P030 Chiller is designed for outdoor operation. The installation altitude must not exceed 2000m
above sea level. The height difference between the installation site of the P030 Chiller and the
COO system separator (Siemens Magnetic Resonance Tomograph) must not exceed −30 to +10
meters.
1.5.2 Operation
The owner or operator of the P030 Chiller has the obligation to establish emergency practices (in
the case of accidents and malfunctions). Based on this Operating Manual, the operator must draw
up a short version of the operating instructions (quick reference guide) and make it available to the
employees.
Notice!
• The quick reference guide must be clearly legible and affixed in the immediate
vicinity of the P030 Chiller.
(See Sample Quick Reference Guide)
• The owner or operator has the obligation to keep a logbook for the P030 Chiller.
he system logbook must either be available on site near the P030 Chiller, or in the event that the
data are stored in a computer of the owner or operator, a printout of the log must be kept in the
vicinity of the P030 Chiller. It must be ensured that these data are accessible to qualified persons
for the performance of repairs and periodical inspections/tests.
1.5.3 Periodical Inspections/Tests
To ensure compliance with minimum safety and health requirements as set forth in standard EN
378, regular tests and inspections of the P030 Chiller are to be carried out by competent persons.
Notice!
• The operator of the unit is responsible for the performance of periodical
inspections and tests.
(See Chapter Periodical Inspections/Tests).