FOR YOUR SAFETY ENGLISH Translation of the Original
8
454522.68.07-01-E
27.06.2012
The water used in the cooling circuit must comply, at a minimum, with the values specified by the
Ordinance on Drinking Water. In the case of de-ionised water, additional constructional features are
necessary.
Based on the drinking water ordinance the following limit values are recommended:
Drinking Water Properties
Appearance: clear, no sediments
Colour: transparent
Ingredients Unit Value
Electric conductivity at 25 °C: µS/cm 80 -750
Hydrogen concentration at 20 °C pH value 6.5 –9.5
Chloride (max.) mg/l 250
Total hardness (min.) °dH 6
Total colony count at 22°C (max.) CFU s/ml 100
1.4 Handling of Refrigerants
Notice!
• When handling refrigerants, all legal provisions and guidelines must be complied
with. Only qualified personnel may perform these activities.
The operator of the P030 Chiller is responsible for the proper disposal of used refrigerants and
system parts.