EasyManua.ls Logo

Riello Array AR 2000 - Page 54

Riello Array AR 2000
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
SHUTDOWN
54
APPENDIX
APPENDIX
Error no. Error Description Checks Solutions
24 FLUE_SWITCH_NOT_CLOSING The blocked ue sensor is not closed
within 10 minutes
25 TSUPPLY_DIFF_ERROR The 2 supply sensors deviate too much for
more than 60 seconds
26 TFLUE_DIFF_ERROR The 2 ue sensors deviate too much for
more than 60 seconds
27 FILLING_TOO_MUCH Too many automated lling attempts in a
short time period
28 FILL_TIME_ERROR Filling takes too long
29 PSM_ERROR Internal software error
30 REGISTER_ERROR Internal software error Replace the power control board
31 T_EXCHANGE_LOCK_ERROR Exchange temperature exceeded the
maximum temperature
32 T_EXCHANGE_DIFF_ERROR The 2 exchange sensors deviate too much
for more than 60 seconds
33 LWCO_1_ERROR Low Water Cut Off 1 error Check the LWCO a- Verify water is in the boiler.
b- Verify good connection between
co
ntrol module and low water probe.
34 LWCO_2_ERROR Low Water Cut Off 2 error a- Check to ensure all valves are
open, pump is running.
b- Check the wiring between the
controller and the LWCO probe.
a- Verify water is in the boiler.
b- Verify good connection between
co
ntrol module and low water probe.
35 GAS_PRESSURE_ERROR Flue pressure switch is closed a- Check gas pressure to ensure
it is steady and within the
recommended range for the unit.
b- Check with as many modules
on as possible to ensure supply
connections are sized properly.
36 AIR_DAMPER_LOCKING Air Damper feedback is not received
when the relative output is open for the
fourth time.
37 FLUE_PRESSURE_LOCKING Flue pressure switch is closed for the
fourth time.
a- Check for obstruction in the
ue piping.
b- Blocking errors should be
recorded prior to the occurrence of
this Locking error.
c- Check for condensate in the
hose connecting the ue pressure
switch to ensure it isn’t blocked.
BLOCKING ERRORS
Error no. Error Description Checks Solutions
100 WD_ERROR_RAM Internal software error Replace the power control board
101 WD_ERROR_ROM Internal software error Replace the power control board
102 WD_ERROR_STACK Internal software error Replace the power control board
103 WD_ERROR_REGISTER Internal software error Replace the power control board
104 WD_ERROR_XRL Internal software error Replace the power control board
105 HIGH_TEMP_ERROR
Supply temperature exceeds 110°C (230°F)
with gas valve closed
a- Check the pump to verify
the ow circulation;
b- Check if the valves on
hy
draulic circuit are open;
c- Check the supply
temperature sensor.
a- Change the pump or restart it;
b- Open the valves on hydraulic circuit;
c- Verify that the temperature sensor
has the correct resistance values. If
values are incorrect sensor must be
replaced.
106 REFHI_TOO_HIGH Internal software error Replace the power control board
107 REFHI_TOO_LOW Internal software error Replace the power control board
108 REFLO_TOO_HIGH Internal software error Replace the power control board
109 REFLO_TOO_LOW Internal software error Replace the power control board
110 REFHI2_TOO_HIGH Internal software error Replace the power control board
111 REFHI2_TOO_LOW Internal software error Replace the power control board
112 REFLO2_TOO_HIGH Internal software error Replace the power control board

Table of Contents

Related product manuals