69
SHUTDOWN
69
APPENDIX
APPENDIX
Menu item Sub item / Parameter Range Default Value Units User level
(138) Appliance Type 50…55 50 2: Installer
(139) Dair active Yes, No No 2: Installer
(140) Minimal Flow 0.0…100 17 l/min 2: Installer
(107) Anti-legionella Day Sun…Sat. Sun Day 2: Installer
(108) Anti-legionella Hour 0…23 0 Hour 2: Installer
(183) High Limit Test Simulated/Physical Simulated 3: Factory
(205) Dep. Zone Control Disabled/Enabled Disabled 1: User
(155) Frost Protection 10…30 15 °C 2: Installer
(186) Frost protection outdoor -30...15 5 °C 2:Installer
Module Cascade Settings
(72) Permit Emergency Mode Yes/No Yes 1: User
(74) Emergency Setpoint 20…90 70 °C 2: Installer
(75) Delay Per Start Next Dep 5…255 120 Sec. 2: Installer
(76) Delay Per Stop Next Dep 5…255 30 Sec. 2: Installer
(142) Delay Quick Start Next 5…255 60 Sec. 2: Installer
(143) Delay Per Quick Stop Next 5…255 15 Sec. 2: Installer
(77) Hyst Down Start Module 0…40 5 °C 2: Installer
(78) Hyst Up Stop Module 0…40 4 °C 2: Installer
(144) Hyst Down Quick Start 0…40 20 °C 2: Installer
(145) Hyst Up Quick Stop 0…40 6 °C 2: Installer
(146) Hyst Up Stop All 0…40 8 °C 2: Installer
(147) Number of Units
1…16 (basic cascade) 1…8
(full cascade)
8 2: Installer
(148) Power Mode
0) Disabled
1) Min burners
2) Max burners
3) Balanced burners
2 2: Installer
(79) Max. Setp. Offset Down 0…40 0 °C 2: Installer