INSTALLATION
INSTALLATION SET-UP
ALL OPERATIONS DESCRIBED IN THIS SECTION MUST BE PERFORMED BY QUALIFIED PERSONNEL
ONLY.
Our Company assumes no liability for damages caused by incorrect connections or operations not
contained in this manual.
UPS STORAGE
The storage site must meet the following requirements:
Degree of relative humidity:
Max relative humidity in operation
90 % (without condensation)
(-1% power for every 100 m above 1000 m)
max 4000 m
Power loss at nominal resistive load
(pf=0.9) and with charged batteries
(1)
2245 kcal/h
8910 B.T.U./h
3140 kcal/h
12460 B.T.U./h
4074 kcal/h
16170 B.T.U./h
4575 kcal/h
18160 B.T.U./h
Installation site fan flow rate for
heat removal
(2)
Current dispersed to ground
(3)
(1) 3.97 B.T.U./h = 1 kcal/h
(2) Use the following formula to calculate air flow: Q [mc/h] = 3.1 x P
diss
[kcal/h] / (t
a
- t
e
) [°C]
P
diss
is power dissipation expressed in kcal/h in the installation site for all installed equipment.
ta= room temperature, te=external temperature. Increase the value derived by 10% to account for losses.
An example of flow is shown in the table, with (t
a
- t
e
)=5°C and with nominal resistive load (pf=0.9).
Notes: The formula applies when ta > te ; if not, the installation requires a conditioner).
(3) The load dispersion current is added to that of the UPS on the ground protection conductor.