PRO-DIALOG+
86
EN
BRODCAST menu
Name Format Default Units Description
ccnbroad 0/1/2 2 - Broadcastactivation
0=disabled
1=broadcastduringholiday,tothenetwork
2=broadcastduringholiday,deviceonly.
oatbusnm 0 to 239 0 - Broadcastofoutdoorairtemperature
Numberofdevicebuseswithoutdoorairtemperature.
oatlocad 0 to 239 0 - Numberofdeviceelementwithoutdoorairtemperature.
dayl_sel Disabled/Enable Disabled - Activation of Summer time / Winter time
Summer time
startmon 1 to 12 3 - Month.
startdow 1 to 7 7 - Dayoftheweek(1=Monday).
startwom 1 to 5 5 - Weekofthemonth.
Winter time
stopmon 1 to 12 10 - Month.
stoptdow 1 to 7 7 - Dayoftheweek(1=Monday).
stopwom 1 to 5 5 - Weekofthemonth.
GENCONF menu
Name Format Default Units Description
lead_cir 0/1/2 0 - Chargingsequenceofcoolingcircuits
0 = automatic
1 = First Circuit A
2 = First Circuit B.
seq_typ No/Yes No - Chargingsequenceforthecoolingcircuit.
ramp_sel No/Yes No - Chargingrampsequence.
off_on_d 1 to 15 1 min Startingdelay.
nh_limit 0 to 100 100 %
Limitationofthepowerthatcanbesuppliedinnightoperationmode.
nh_start 00:00 to 24:00 00:00 - Starttimeofnightoperationmode.
nh_end 00:00 to 24:00 00:00 - Endtimeofnightoperationmode.
bas_menu 0 to 3 0 -
Basicmenuaccessconguration
0 = full access
1=accesstotheAlarmmenuwithpassword
2=accesstotheSetpointmenuwithpassword
3=combinationof1and2.
synoptic No/Yes No - Displayofsynopticchart
PUMPCONF menu
Name Format Default Units Description
pump_seq 0/1/2/3/4 0 - Heatexchangerpumpsequence
0 = no pump
1 = one pump
2=twopumpswithautomaticswitching
3 = manual selection of pump 1
4 = manual selection of pump 2.
pump_del 24 to 3000 48 hours Intervalbetweenpumpswitching.
pump_per No/Yes No - Protectionagainstpumpmechanicallock.
pump_sby No/Yes No - Pumpstopwhendeviceisinstand-bymode.
pump_loc No/Yes Yes - Waterowratecheckwhenpumpisstopped.
HCCONFIG menu
Name Format Default Units Description
auto_sel No/Yes No - Automaticswitchingselection.
cr_sel 0 to 2 0 - Compensationselectionincoolingmode.
hr_sel 0 to 2 0 - Selection1ofcompensationinheatingmode.
1=accordingtooutsidetemperature
0 = none
2=accordingtotemperaturedifference
heat_th -20 to 0 -15 °C Outsidetemperaturethresholdforcoolingmode.
boil_th -15 to 15 -10 °C Outsidetemperaturethresholdforheatgenerator.
ehs_th -5 to 21.2 5 °C Outsidetemperaturethresholdforadditionalelectricheating.
both_sel No/Yes No - Heating or cooling control selection for HSM.
ehs_back No/Yes No - Firstbackupstepoftheadditionalelectricheating.
ehs_pull 0 to 60 0 minutes Activationdelayofrstadditionalelectricheatingstep.
ehs_defr No/Yes No - Fastdefrostwithadditionalelectricheatinguse.