PRO-DIALOG+
90
EN
HEATINGSTANDBYCOOLING
Outdoor
temperature
* This threshold is not applicable for the machines of NXC series.
Heating
threshold
Cooling
threshold
PARAMETER CONDITION
ON/OFF STATUS CONTROL TYPE HEATING / COOLING
LOCAL MODE
SELECTION
HEATING / COOLING
Remote CONTACT
HC_SEL OUTSIDE TEMPERATURE OPERATING
METHOD
Off - - - - - Heating
On Local Cooling - - - Heating
On Local Heating - - - Cooling
On Local Active - - >Coolingthreshold Heating
On Local Auto - - <Heatingthreshold Heating*
On Local Auto - - Betweenheatingandcoolingthresholds Standby
On Remote Auto Coolingmode - - Heating
On Remote - Heatingmode - - Heating
On Remote - Automode - >Coolingthreshold Heating
On Remote - Automode - <Heatingthreshold Heating*
On Remote - Automode - Betweenheatingandcoolingthresholds Standby
On RCN - -
Cooling
- Heating
On RCN - - Heating - Heating
On RCN - - Auto >Coolingthreshold Heating
On RCN - - Auto <Heatingthreshold Heating*
On RCN - - Auto Betweenheatingandcoolingthresholds Standby
3.5.3 Heating/cooling/stand-by mode
SwitchingfromonemodetotheotherispossibleforallNXH/
NXC units but only the NXH versions can switch to heating
mode. There is also the possibility to automatically switch
fromcoolingtoheatingmode.
Thisisdecidedbytheexternalprobethatthroughtwopre-
setthresholdvalues(heatand coolthresholds) adjusts the
machine operation.
Beforeswitchingfromheatingtocoolingmode,theunitgo-
esrstinstandbymode;inthiscaseitiselectricallypowe-
redbutthecompressorisatastandstill.Thediagrambelow
showswhatsaidsofar.
Thetablebelowcompares,accordingtothemachinesta-
tusandcontroltype,theparametersthatmanagetheau-
tomatic Cooling/Heating/Standby switching according to
thedifferentmodes,whicharenamely:
Localmode:Switchingismanagedfromtheunitcon-
trol panel.
Contacts:Switchingismanagedthroughthecontacts.
Thecontrolmustbeoftheremotetype.
HC_SEL:Switchingismanagedifthecontroltypeisofthe
CRNtype.
* Not applicable to NXC series machines.